毕业论文论文范文课程设计实践报告法律论文英语论文教学论文医学论文农学论文艺术论文行政论文管理论文计算机安全
您现在的位置: 毕业论文 >> 英语论文 >> 正文

土木工程建筑外文文献及翻译 第3页

更新时间:2010-5-15:  来源:毕业论文
土木工程建筑外文文献及翻译 第3页
3. Experimental program
The experimental set-up for studying the behavior of a connection was based on Fig. 6(a). Using the plastic displacement dp, plastic rotation gp, and plastic story drift angle qp shown in the figure, from geometry, it follows that:
 And:
in which d and g include the elastic components. Approximations as above are used  for large inelastic beam deformations. The diagram in Fig. 6(a) suggest that a sub  assemblage with displacements controlled in the manner shown in Fig. 6(b) can  represent the inelastic behavior of a typical beam in a CGMRF.
The test set-up shown in Fig. 8 was constructed to develop the mechanism shown  in Fig. 6(a) and (b). The axial actuators were attached to three  2438 mm × 1219 mm × 1219 mm (8 ft × 4 ft × 4 ft) RC blocks. These blocks were  tensioned to the laboratory floor by means of twenty-four 32 mm diameter dywidag  rods. This arrangement permitted replacement of the specimen after each test.
Therefore, the force applied by the axial actuator, P, can be resolved into two or thogonal components, Paxial and Plateral. Since the inclination angle of the axial actuator does not exceed 3.0, therefore Paxial is approximately equal to P [4]. However, the lateral component, Plateral, causes an additional moment at the beam-to column joint. If the axial actuators compress the specimen, then the lateral components will be adding to the lateral actuator forces, while if the axial actuators pull the specimen, the Plateral will be an opposing force to the lateral actuators. When the axial actuators undergo
  axial actuators undergo a lateral displacement _, they cause an additional moment at the beam-to-column joint (P-△ effect). Therefore, the moment at the beam-to column joint is equal to:
where H is the lateral forces, L is the arm, P is the axial force and _ is the lateral displacement.
 Four full-scale experiments of beam column connections were conducted.
The member sizes and the results of tensile coupon tests are listed in Table 2
All of the columns and beams were of A572 Grade 50 steel (Fy   344.5 MPa). The actual measured beam flange yield stress value was equal to 372 MPa (54 ksi), while the  ultimate strength ranged from 502 MPa (72.8 ksi) to 543 MPa (78.7 ksi).
Table 3 shows the values of the plastic moment for each specimen (based on  measured tensile coupon data) at the full cross-section and at the reduced section at  mid-length of the RBS cutout.
The specimens were designated as specimen 1 through specimen 4. Test specimens details are shown in Fig. 9 through Fig. 12. The following features were utilized in the design of the beam–column connection:
 The use of RBS in beam flanges. A circular cutout was provided, as illustr- ated in Figs. 11 and 12. For all specimens, 30% of the beam flange width was removed.  The cuts were made carefully, and then ground smooth in a direct- tion parallel to the beam flange to minimize notches.
Use of a fully welded web connection. The connection between the beam web and the column flange was made with a complete joint penetration groove weld  (CJP). All CJP welds were performed according to AWS D1.1 Structural Welding Code
Use of two side plates welded with CJP to exterior sides of top and bottom beam flan- ges, from the face of the column flange to the beginning of the RBS, as shown  in Figs. 11 and 12. The end of the side plate was smoothed to meet the beginning of the RBS. The side plates were welded with CJP with the column flanges. The  side plate was added to increase the flexural capacity at the joint location, while  the smooth transition was to reduce the stress raisers, which may initiate fracture
Two longitudinal stiffeners, 95 mm × 35 mm (3 3/4 in × 1 3/8 in), were welded with 12.7 mm (1/2 in) fillet weld at the middle height of the web as shown in  Figs. 9 and 10. The stiffeners were welded with CJP to column flanges.
Removal of weld tabs at both the top and bottom beam flange groove welds. The weld tabs were removed to eliminate any potential notches introduced by the tabs  or by weld discontinuities in the groove weld run out regions
Use of continuity plates with a thickness approximately equal to the beam flange thickness. One-inch thick continuity plates were used for all specimens.
While the RBS is the most distinguishing feature of these test specimens, the longitudinal stiffener played an important role in delaying the formation of web local buckling and developing reliable connection performance

上一页  [1] [2] [3] [4] [5] [6] [7] [8] [9] 下一页

土木工程建筑外文文献及翻译 第3页下载如图片无法显示或论文不完整,请联系qq752018766
设为首页 | 联系站长 | 友情链接 | 网站地图 |

copyright©youerw.com 优文论文网 严禁转载
如果本毕业论文网损害了您的利益或者侵犯了您的权利,请及时联系,我们一定会及时改正。